THE Y343B IGNITION PACKAGE PROVIDES
DIRECT SPARK IGNITION (DSI) FOR GAS
HEATING SYSTEMS. THE PACKAGE IN
CLUDES THE S87D ELECTRONIC MODULE,
Q354A FLAME SENSOR, Q347A SPARK IG
NITER-SENSOR AND 392286-1 IGNITION
CABLE.
DEPENDABLE BURNER IGNITION
Spark generated by electronic module and
internal step-up transformer.
SOLID STATE DESIGN
Compact, solid state components provide
accurate, long-lasting performance.
No mechanical friction or wear.
MAXIMUM OPERATING SAFETY
Proves presence of flame on burner igni
tion, then protects against burner flame-out
and interruption of electric power or gas sup
ply during run cycle.
Open or short circuit in any electronic com
ponent results in safety shutdown.
USES FLAME RECTIFICIATION PRINCIPLE
Any false flame signal, including electrical
short or ground, results in safety shutdown.
Ignition is started, main burner is ignitied,
burner flame is proved and continuously
monitored during main burner-on period. Ig
nition spark is discontinued when flame is
proved.
CONVENIENT REMOTE
RESTART PROCEDURE
After safety shutdown, equipment must be
manually reset from remote thermostat or
temperature controller.
System automatically locks out after
trial-for-ignition. If malfunction exists, correc
tion must be made before system is manually
reset.
LOW VOLTAGE CONTROL CIRCUIT
Permits use of 24 V thermostat for op
timum temperature control.
Reduced wiring costs both on appliance
and on job.
GAS VALVE CONTROL
S87D internal relay switches the gas valve
on and off.
System can be used with a 2-stage gas
valve, if desired.
ALARM CONTROL
Optional alarm circuit provides 24 Vac for
an automatic visual or audible signal if any
part of system malfunctions and causes a
lockout.
Y343B1002
L.H.
1-83»
Form Number 68-0014
©Honeywell Inc. 1983
Vista de página 0
1 2 3 4 5 6 ... 10 11

Resumo do Conteúdo

Página 1 - Honeywell

HoneywellTHE Y343B IGNITION PACKAGE PROVIDES DIRECT SPARK IGNITION (DSI) FOR GAS HEATING SYSTEMS. THE PACKAGE INCLUDES THE S87D ELECT

Página 2 - ORDERING INFORMATION

GROUNDING CONNECTIONSA common ground is required for the burner, spark igniter-sensor mounting bracket and the GND terminal of the S87. If ground is

Página 3 - Q354A FLAME SENSOR

start the system by setting the thermostat (temperature controller) to call tor heat. Observe the system response and establish the type

Página 4 - INSTALLATION

The Y343B1002 Direct Spark Gas Burner Ignition Package includes the S87D Electronic Module, Q347A Spark Igniter-Sensor, Q354A Flame Se

Página 5

AMBIENT TEMPERATURE RATING: Minus 40 F to plus 175 F [minus 40 C to plus 79 C].WIRING CONNECTIONS: 1/4 in. [6.4 mm] male quick-connect ter

Página 6

TABLE 1—GAS CONTROLS.MODEL NO.TYPE OF PRESSURE REGULATORCAPACITY RANGE OF STANDARD MODELPUBLICATION FORM NUMBERcfh mVhrV845AStandard noto 335 3.1 to 9

Página 7 - O A S COWTROL—

Position the Q347 so that only the tips of the electrodes are immersed in the burner flame. The burner must ignite smoothly — usually this wi

Página 8

Q354A FLAME SENSOR1. Mate quick-connect terminals (1/4 in. [6.4 mm})' are provided on both the Q354 and S87D. Connect the SENSOR terminal on

Página 9 - IGNITION CABLE

FIG. 6—WIRING HOOKUP FOR Y343B PACKAGE IN A TYPICAL TWO-STAGE DSI HEATING SYSTEM.ANY DUAL VALVE • - O A S COWTROL—-A \ POWER SUPPLY. PROVIDE DISCONN

Página 10 - CHECKOUT AFTER SERVICE

The following start-up and checkout procedures are basic to the S87. If possible, refer to the specific instructions provided by the appl

Página 11 - PRINTED IN U.S.A

1J TEMPERATURE CONTROLLER CALLS FOR HEAT-1i / SVS' POwPOWER INTERRUPTION >SVSTLM SHUTS OFF, RESTARTS WHEN POWER IS RESTORED.0”SPARK GENERA

Comentários a estes Manuais

Sem comentários