Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 1 07/09
3 Operation A Display Panel C DIP Switch Setting A 20-segment Bargraph Display indicates the gas concentration level. The bottom LED is always lit
3 Operation continued D Signal and Setpoints The voltage between TP Gnd and TP Sig indicates the current signal received from the sensor. The norma
3 Operation continued G Maintenance The Manning GM-1 is designed for long life and high reliability. Honeywell Analytics recommends checking signal
4 Limited Warranty 1. Limited Warranty Honeywell Analytics, Inc. warrants to the original purchaser and/or ultimate customer (“Purchaser”) of Mann
Notices and Trademarks Copyright 2009 by Honeywell International Inc. Release D July 2009 While this information is presented in good faith and beli
About This Document World Wide Web The following Honeywell web sites may be of interest. Honeywell Organization WWW Address (URL) Corporate www.h
Contents Serial number: Section Title Page 1 System Description 5 2 Installation 7 3 Operation 10 4 Limited Warranty 13 Introduction
1 System Description The Manning GM-1 is designed to accept a single 4/20 mA current input signal, plus provide a regulated 24 VDC supply to operat
1 System Description continued System Specifications Electrical Power: 120 VAC, 50/60 Hz at 0.35 amp (230 VAC 50/60 Hz is available as an option)
2 Installation A Locating the Manning GM-1 Figure 1: Mounting dimensions for the Manning GM-1 Gas Monitoring Alarm System When unpacking the unit, i
2 Installation continued B Wiring Relay Wiring: All three relays have Form C, dry contacts. Any required power source must be within the 3 amp rati
2 Installation continued Figure 2: Wiring diagram for the Manning GM-1 Gas Monitoring Alarm System NO NCC NO NCC NO NCCLNWARNINGRELAY*120 VACWARNIN