21 69-0643—1
Voltage At Timer Terminals
AC Voltages at
C-C Terminals Check Action
0 Vac. System power off. Restore power.
Short in timer power supply wiring. Replace wiring.
Limit switch contacts stuck open. Free or replace limit switch.
Transformer supplying power is Replace transformer.
burned out.
Up to 15 Vac. System transformer used to power Use additional (separate)
the timer is inadequate. transformer.
Additional (separate) transformer Install transformer with proper
used to power the timer has secondary voltage.
inadequate voltage.
15 to 30 Vac. Spring fingers on thermostat not Rebend spring fingers to a 45
making proper contact with subbase degree angle to assure proper
terminals. contact.
Timer has failed. Replace thermostat.