Troubleshooting
(continued)
1 Not applicable on heating-only model.
Problem Check Action
Heat-on time too short. anticipator setting. (See Fig. 6 for
anticipator location.)
Increase anticipator setting by 0.05.
Observe heating system operation.
Heat-on time too long. anticipator setting. (See Fig. 6 for
anticipator location.)
Decrease anticipator setting by 0.05.
Observe heating system operation.
No cooling. system switch. May be in OFF or
HEAT position.
Move switch to COOL position.
fuse or circuit breaker. If fuse is blown or breaker tripped,
replace or reset.
condenser switch position.
Located outdoors and may be
turned Off.
Move to ON position.
Y, G, RC thermostat connections. Turn Off power to cooling system. Check
for correct terminal hookups. Repair any
frayed or broken wires. Firmly tighten all
terminal screws.