INSTALLATION INSTRUCTIONS
69-1414-2
T8611G Chronotherm
®
Deluxe Zoning
Heat Pump Thermostat
APPLICATION
The T8611G Chronotherm® Deluxe Zoning Heat Pump Thermostat provides electronic control of 24 Vac zoned heat
pump systems. Refer to Table 1 and Table 2 for a general description of the thermostat and zoning applications.
Table 1. Description of T8611 Thermostats.
Table 2. T8611 Zoning Applications.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 1.5m (5 ft) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
drafts, or dead spots behind doors and in corners.
hot or cold air from ducts.
radiant heat from sun or appliances.
concealed pipes and chimneys.
unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
Position wallplate horizontally on the wall or on a
2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions correctly even
when not level.
2. Use a pencil to mark the mounting holes.
See Fig. 2.
Model Power Method Changeover System Selection Fan Selection
T8611G2051 Hardwired Automatic or manual Heat-Off-Cool-Auto-Em. Heat On-Auto
Model TotalZone
®
EMM-3U EMM-3
T8611G2051 Yes Yes No
Vista de página 0
1 2 3 4 5 6 ... 11 12

Resumo do Conteúdo

Página 1 - Heat Pump Thermostat

® U.S. Registered TrademarkCopyright © 2003 Honeywell • • All Rights Reserved INSTALLATION INSTRUCTIONS69-1414-2T8611G Chronotherm®Deluxe ZoningHe

Página 2 - 69-1414—2 2

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT69-1414—2 10NOTE: Press any key and the displayed numbers will change. Press Time ∇ to go to the

Página 3 - Mounting Thermostat

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT11 69-1414—2TROUBLESHOOTING GUIDE (TABLE 7)Table 7. Troubleshooting Guide.Symptom Possible Cause

Página 4 - SETTINGS

69-1414—2 G.H. Rev. 1-03 www.honeywell.com/yourhomeT8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTATPrinted in U.S.A. on recycled paper cont

Página 5 - INSTALLER SETUP

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT69-1414—2 2Fig. 1. Typical location of thermostat.Fig. 2. Mounting the wallplate.3. Remove the w

Página 6 - 69-1414—2 6

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT3 69-1414—2Fig. 4. Typical wiring diagram for T8611G on TotalZone® Control Panel.Fig. 5. Correct

Página 7 - 7 69-1414—2

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT69-1414—2 4Fig. 7. T8611G key locations and descriptions.Using Thermostat KeysThe thermostat key

Página 8 - View or Reset Timer Settings

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT5 69-1414—2INSTALLER SETUPThe Installer Setup is used to customize the thermostat to specific sy

Página 9 - INSTALLER SELF-TEST

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT69-1414—2 6Degree temperature display14 0 Temperature is displayed in °F1 Temperature is display

Página 10 - CHECKOUT

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT7 69-1414—2IMPORTANTReview the settings to confirm that they match the system. Press Run Program

Página 11 - 11 69-1414—2

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT69-1414—2 8Setting Current Day and Time1. Press Set Current Day/Time.NOTE: On initial powerup or

Página 12 - Printed in U.S.A. on recycled

T8611G CHRONOTHERM® DELUXE ZONING HEAT PUMP THERMOSTAT9 69-1414—2INSTALLER SELF-TESTUse the Installer Self-Test to check the thermostat operation. Ref