D Note the tabs on the top inside edge of the ther
mostat base. These fit the slots molded into the top of
the wailplate or subbase.
n Hang thermostat base on wailplate or subbase.
6 MOUNT THE THERMOSTAT—-----------------
! I Insert the two captive mounting screws located in
the bottom corners of the base (Fig. 5).
Q Firmly tighten screws.
7 SET HEAT ANTICIPATOR----------------------
n Make sure you know the current draw (anticipator
setting] for your system. This information can be found
printed on the primary control at the furnace or on the
furnace output/listing label. However, it is good in
stallation practice to physically test the heating primary
current draw before setting the heat anticipator. This is
done by connecting the R and W terminals through a
suitable meter (0-5 A), or with thermostat wire held
through a clamp on meter using multiple loops to mag
nify the field (ten [oops are typically used so meter read
ing can be divided by ten). Physical measurement is
urged, as modern HVAC equipment typically incor
porates multiple control circuit loads, and accurate
anticipator setting prevents poor control and callbacks.
Move heat anticipator lever to match the current
draw (Fig. 6), except in single-stage heat pump sys
tems. In these systems, set the anticipator at 1.4 times
the actual current draw to reduce the cycling rate.
anticipator
5CALEPLATE
ANTICIPATOR
SETTING
LEVER
OIL BURNER CONTROL
SHOWS
ANTICfPATOn
SHOWS
ANTICIPATOfl-
SETTIKG
SHOWS
ANTICIPATOR
SETTfNG
ZONE VALVE
TYPICAL GAS VALVE
Fig. 6—Setting heat anticipator.