PRODUCT DATA® U.S. Registered TrademarkCopyright © 1997 Honeywell Inc. • All Rights ReservedD896 Automatic Vent DamperGENERALD896 Automatic Vent D
D896 AUTOMATIC VENT DAMPER68-018610ANSI STANDARDSEXHIBIT AProcedure For Safety Inspection of an Existing Appliance InstallationThe following procedure
D896 AUTOMATIC VENT DAMPER68-018611EXHIBIT BProcedure for Installing Electrically Operated Automatic Vent Damper Devices on Existing AppliancesThis pr
D896 AUTOMATIC VENT DAMPER68-018612Honeywell Europe S.A.3 Avenue du BourgetB-1140 Brussels BelgiumHoneywell Asia Pacific Inc.Room 3213-3225Sun Hung Ka
D896 AUTOMATIC VENT DAMPER68-01862ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRADELINE® wholesaler or distri
D896 AUTOMATIC VENT DAMPER68-01863NOTE: A minimum of a 30 VA transformer must be usedwhen D896 is installed with S86/S8600/S8610/S8620.Electrical Conn
D896 AUTOMATIC VENT DAMPER68-01864IMPORTANT1. The atmospheric draft hood outlet area must besmaller or equal to the inlet area of the damperassembly.2
D896 AUTOMATIC VENT DAMPER68-01865Fig. 3. Installing D896 Vent Damper.IMPORTANTNever mount the vent damper with the motoractuator above or below the v
D896 AUTOMATIC VENT DAMPER68-01866Fig. 5. D896 with cover off.HoneywellD892/D896WiresHoneywellD80B WiresJohnsonQ35 WiresEFFIKALRVG WiresYellow Orange
D896 AUTOMATIC VENT DAMPER68-01867MV MV/PV PVGND(BURNER)24VGND24V SPARKS8600F, H, M; S8610F,HPOWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PRO
D896 AUTOMATIC VENT DAMPER68-01868Fig. 10. Snap-Tite™ Box Connector release.CheckoutHeating1. Turn on the power supply.2. If using a thermostat, set t
D896 AUTOMATIC VENT DAMPER68-01869Thermostat Setting Symptom Possible Cause ActionSet thermostat 10°Fabove room temperatureto call for heat.No respons