INSTALLATION INSTRUCTIONS
Copyright © 1996 Honeywell Inc. • • All Rights Reserved
T874H,Q,W Multistage Thermostats and
Q674B,C,G,L Subbases
APPLICATION
The T874H,Q,W Multistage Thermostats provide 24 to 30
Vac control for heating and cooling systems as listed in
Table 1.
Table 1. Heating and Cooling Stages.
a
Plus a changeover stage that operates with cooling.
The Q674B,C,G,L Subbases provide wiring terminals,
system and fan switching, and mounting bases for T874
Multistage Thermostats as listed in Table 2.
Table 2. Switching Positions.
OPERATION
On a two-stage or three-stage heat thermostat, the stages
of heat
make
sequentially as the temperature drops.
Make
refers to the mercury switch initiating a call for heat or cool.
There are about 2°F (1°C) between the stages so that the
second stage makes only when the first stage can not
handle the load. About one degree later, the third stage
makes (T874W only). This degree difference is called the
interstage differential
.
Select models include LEDs (light-emitting diodes). The
LED lights to indicate a problem with the system; refer to
the system manufacturer instructions.
When an LED lights, refer to this list for the meaning:
FILTER: clogged filter needs replacement.
EM. HT.: emergency heat is operating. The compressor
has failed, and the heat pump is not operating. The
LED lights when the homeowner places the system
switch in the EM. HT. position.
AUX. HT.: auxiliary heat is operating because the
weather is so cold that the heat pump alone cannot
handle the load.
SERVICE or CHECK: system needs to be checked.
See heating system instructions for specific
meaning.
LEDs are not field addable or replaceable.
RECYCLING NOTICE
This control contains mercury in a sealed tube. Do
not place the control in the trash at the end of its
useful life.
If this control is replacing a control that contains
mercury in a sealed tube, do
not
place your old
control in the trash.
Contact your local waste management authority for
instructions regarding the recycling and the proper
disposal of this control, or of an old control
containing mercury in a sealed tube.
INSTALLATION
When Installing this Product…
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.
69-0087-6
T874 Model
Stage H
a
QW
Heating Stages 1 1 3
Cooling Stages 1 2
Q674
Switch Positions
Model
System Fan
B Heat-Off-Cool Auto-On
C Off-Auto Auto-On
G Off-Auto None
L Em Ht-Heat-Off-Cool Auto-On
Vista de página 0
1 2 3 4 5 6 7 8

Resumo do Conteúdo

Página 1 - Q674B,C,G,L Subbases

X-XX ULINSTALLATION INSTRUCTIONSCopyright © 1996 Honeywell Inc. • • All Rights ReservedT874H,Q,W Multistage Thermostats andQ674B,C,G,L S

Página 2 - Location

69-0087—62T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASESM6009VERTICAL OUTLETBOXADAPTERRINGCOVER PLATEMOUNTINGSCREWS (2)1SUBBASESUBBASEMOUNT

Página 3 - 69-0087—6

69-0087—63T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASESFOR STRAIGHTINSERTION–STRIP 5/16 in. (8 mm)FOR WRAPAROUND–STRIP 7/16 in. (11 mm)SUB

Página 4

69-0087—64T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASESL21OFFH1 ANTICIPATORH2 ANTICIPATORH11POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OV

Página 5

69-0087—65T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASES1L1(HOT)L2TW3UGRELXBOY1Y2C815A OD THERMISTORAUX. HEAT RELAYFAN RELAYEM. HEAT RELAYC

Página 6 - Mounting the Thermostat

69-0087—66T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASESFig. 9. T874W/Q674L for three-stage heat and two-stage cool with outdoor reset.1TW3

Página 7 - CHECKOUT

69-0087—67T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASESTHERMISTOR RESISTANCEC815A THERMISTOR RESISTANCER = 400 ohms ± 10% AT 77°F (25°C)46

Página 8 - CALIBRATION

69-0087—68T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASESHoneywell Limited-Honeywell Limitée35 Dynamic DriveScarborough, OntarioM1V 4Z9Autom