PRODUCT DATA
65-0214-08
V4943/V8943B,C,N;
V4944/V8944B,C,L,N
Regulating Diaphragm Gas Valves
APPLICATION
The V4943/V8943B and N (single stage) and V4944/V8944B
and N (two stage) are solenoid-operated diaphragm valves
suitable for natural gas only. The V4943/V8943C and
V4944/V8944C and L are solenoid-operated diaphragm
valves suitable for Liquefied Petroleum (LP) gas only. These
valves are used on boilers, unit heaters, duct furnaces,
makeup air and rooftop heaters.
FEATURES
Models are available for natural or liquid petroleum
(LP) gases.
Valve models L, N are rapid opening (less than six
seconds) and fast closing, and are available for LP and
natural gases, respectively.
Line voltage with two-wire thermostat or controller is
used with V4943; V8943 is used with 24V thermostat or
controller.
V4944 is used with line voltage dual-stage thermostat
or controller; V8944 is used with 24V dual-stage
thermostat or controller.
Slow opening B,C valve models are available for
natural and LP gases respectively.
Valve closes on power failure; recommended for final
shutoff service.
Valve closing time: 2 seconds maximum at 7 inches wc
inlet pressure.
Valves rated for 0.5 pound per square inch (psi) (3.4
kPa).
Leadwires and cover for electrical conduit connections
are provided.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 6
Operation .......................................................................... 9
Checkout and Troubleshooting ......................................... 10
Service Information .......................................................... 12
Vista de página 0
1 2 3 4 5 6 ... 11 12

Resumo do Conteúdo

Página 1 - V4944/V8944B,C,L,N

PRODUCT DATA65-0214-08V4943/V8943B,C,N; V4944/V8944B,C,L,N Regulating Diaphragm Gas ValvesAPPLICATIONThe V4943/V8943B and N (single stage) and V4944/V

Página 2 - SPECIFICATIONS

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES65-0214—08 10Operation of the V4943B,C,N/V8943B,NThe V4943/V8943B,C,N Valves are c

Página 3 - 3 65-0214—08

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES11 65-0214—08Checkout1. Valve outlet pressure measurements are made at a point app

Página 4 - Gas Valve Sizing

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVESAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive Nor

Página 5 - PRESSURE DROP (IN. WC)

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES65-0214—08 2ORDERING INFORMATIONWhen purchasing replacement and modernization prod

Página 6 - INSTALLATION

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES3 65-0214—08Pressure Reference Port Vent: 5/16–24 UNF internal tapping.Standard Fa

Página 7 - 7 65-0214—08

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES65-0214—08 4Fig. 1. V4943/44 and V8943/44 dimensions in in. (mm).Gas Valve Sizing1

Página 8 - 65-0214—08 8

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES5 65-0214—08Fig. 3. Capacity vs. pressure drop of Natural Gascurves for 1-1/4 in.

Página 9 - OPERATION

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES65-0214—08 6Fig. 7. Capacity vs. pressure drop of LP Gascurves for 1-1/4 in. valve

Página 10 - TROUBLESHOOTING

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES7 65-0214—08When Installing this Product...1. Read these instructions carefully. F

Página 11 - Checkout

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES65-0214—08 8Fig. 10. Preparing the piping and installing the valve.WiringWARNINGEl

Página 12 - SERVICE INFORMATION

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES9 65-0214—08Fig. 11. Typical wiring diagram for V4943B,N.Fig. 12. Typical wiring d